Characteristics of Cold Storage Fires
1. Traditional detectors are unusable
Traditional fire detectors are not suitable for installation inside cold storage facilities. Due to the extremely low temperatures inside, the detectors would frost over or malfunction.
2. Numerous fire hazards
Electrical or mechanical malfunctions in air conditioning and refrigeration equipment, cargo handling equipment, and lighting equipment, as well as the presence of polystyrene foam insulation materials, plastic packaging materials, and wooden pallets, all contribute to fire hazards inside cold storage facilities. The extremely low temperatures cause the plastic sheathing of electrical cables to become brittle and easily damaged, leading to short circuits and fires. Furthermore, the air inside cold storage facilities is exceptionally dry, resulting in very rapid fire spread once a fire starts.
3. Difficult to extinguish fires
The enclosed space of cold storage facilities traps smoke, which lingers for extended periods. Fires spread rapidly along the insulation materials, and the large internal space and numerous shelves make it difficult for water hoses to reach and cool the fire source.
Solutions for Cold Storage Fires
High-sensitivity air sampling smoke detectors can be used in cold storage applications. The detection unit can be installed outside the cold storage facility, with air sampling tubes extending into the interior. The high-efficiency suction pump inside the detection unit draws air samples from the cold storage facility through the sampling tubes back to the detection unit for smoke detection, overcoming the problem of detectors malfunctioning due to the low temperatures inside the cold storage. Additionally, because AVA air sampling smoke detectors have very high sensitivity (more than 1000 times that of traditional smoke detectors), they can provide early warning signals in the initial stages of a fire.
Under the ceiling
The spacing of sampling holes is recommended to be within 6m, which is equivalent to a protected area of 36m2 per sampling hole.
In cold storage facilities with shelves and ceiling heights exceeding 12m, sampling tubes should be installed at different heights. For example, if the ceiling height is 14m, sampling tubes should be installed along the shelves at a height of approximately 7m.
Return air vents
Return air sampling can provide excellent early smoke detection, especially in low-temperature environments like cold storage facilities. High-temperature smoke particles lose their upward thermal buoyancy after being cooled by the ambient temperature and are easily carried to the return air vents by the airflow generated by the air conditioning system.